Carrier Weathermaster 48HJD Series Product Data page 29

Single-package rooftop units high-efficiency electric cooling/ gas heating
Table of Contents

Advertisement

COOLING CAPACITIES, UNITS WITH MOISTUREMISER OPTION (cont)
48HJ006 (5 TONS)
Temp (F)
1500/0.08
Air Ent
Condenser
(Edb)
72
67
TC
69.9
62.7
75
SHC
29.0
36.9
kW
3.61
3.55
TC
65.9
59.1
85
SHC
25.3
34.0
kW
4.05
3.97
TC
61.9
55.2
95
SHC
21.6
31.1
kW
4.53
4.43
TC
57.7
51.1
105
SHC
18.1
27.8
kW
5.05
4.93
TC
53.4
47.2
115
SHC
14.7
24.6
kW
5.60
5.49
TC
48.7
42.0
125
SHC
10.9
19.6
kW
6.26
6.12
48HJ007 (6 TONS)
Temp (F)
1800/0.05
Air Ent
Condenser
(Edb)
72
67
TC
82.6
75.6
75
SHC
36.0
44.8
kW
4.60
4.52
TC
78.2
71.6
85
SHC
31.4
41.2
kW
5.16
5.03
TC
73.8
67.4
95
SHC
27.0
37.6
kW
5.75
5.60
TC
68.4
62.6
105
SHC
22.3
33.5
kW
6.37
6.22
TC
63.4
57.8
115
SHC
18.1
29.5
kW
7.04
6.89
TC
55.5
49.6
125
SHC
15.3
24.0
kW
7.80
7.61
LEGEND
BF
— Bypass Factor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW
— Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
Temp (F) Air Entering Evaporator — Cfm/BF
1750/0.09
Temp (F) Air Entering Evaporator — Ewb
62
72
67
62
56.2
74.7
67.3
61.0
43.9
31.7
40.5
51.2
3.51
3.64
3.58
3.49
51.7
70.6
63.2
56.3
41.9
27.5
37.6
48.0
3.91
4.07
4.01
3.92
47.7
66.5
58.8
51.3
40.0
23.5
34.5
44.6
4.35
4.55
4.47
4.37
44.9
61.8
54.5
47.7
35.7
20.0
31.2
40.1
4.84
5.09
4.97
4.88
42.0
56.6
50.0
44.2
31.5
16.5
27.8
35.7
5.40
5.64
5.52
5.45
36.9
51.3
45.0
39.0
28.0
12.5
22.2
31.5
6.02
6.28
6.18
6.09
Temp (F) Air Entering Evaporator — Cfm/BF
2100/0.06
Temp (F) Air Entering Evaporator — Ewb
62
72
67
62
68.5
84.9
78.0
70.9
55.4
37.5
49.1
59.7
4.36
4.67
4.57
4.46
64.5
80.9
73.4
65.8
51.7
33.0
44.7
55.8
4.89
5.22
5.11
4.96
60.2
76.3
68.3
60.5
47.9
28.2
40.0
51.6
5.44
5.80
5.66
5.48
55.9
71.4
64.3
56.2
43.5
23.4
36.5
48.0
6.06
6.45
6.27
6.10
50.7
66.0
60.1
51.5
38.9
18.8
32.9
44.1
6.68
7.10
6.91
6.74
45.8
58.4
52.4
46.1
35.2
15.7
27.5
39.0
7.38
7.83
7.67
7.49
2000/0.11
2500/0.13
72
67
62
72
78.5
71.2
64.8
81.7
34.5
44.2
55.4
37.8
3.65
3.60
3.51
3.62
75.5
66.8
60.7
78.1
30.7
41.6
52.0
33.8
4.11
4.00
3.95
4.08
70.4
61.9
55.7
74.2
26.0
38.6
47.9
30.0
4.56
4.42
4.41
4.58
65.1
57.2
50.8
68.4
22.1
34.3
43.5
26.1
5.11
4.96
4.92
5.11
59.6
52.5
46.2
62.6
18.2
30.0
39.0
22.1
5.69
5.55
5.48
5.69
54.1
46.8
40.9
56.9
13.5
24.0
34.0
16.5
6.33
6.18
6.13
6.33
2400/0.06
3000/0.08
72
67
62
72
85.9
79.5
73.5
89.1
38.8
51.1
64.0
41.8
4.70
4.57
4.45
4.77
82.0
74.4
67.9
85.8
34.7
47.4
60.1
37.6
5.26
5.09
4.97
5.32
77.5
69.3
62.3
82.0
30.2
43.7
56.2
33.6
5.84
5.68
5.53
5.90
72.1
64.6
58.3
75.7
25.4
38.4
50.2
29.1
6.46
6.29
6.16
6.53
66.4
59.6
54.5
68.8
20.7
33.3
43.8
24.3
7.12
6.95
6.83
7.16
57.6
52.1
49.5
59.2
17.5
27.5
38.4
20.9
7.89
7.72
7.58
7.92
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t ldb = t edb –
t lwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h lwb )
h lwb = h ewb –
Where: h ewb = Enthalpy of air entering evaporator coil.
3. The SHC is based on 80 F edb temperature of air entering evapo-
rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
67
62
75.5
69.3
52.0
62.8
3.58
3.51
70.8
65.1
47.4
58.0
4.02
3.96
65.9
60.6
42.8
52.6
4.49
4.44
60.3
56.1
38.9
48.5
5.03
4.98
54.9
51.6
34.9
44.3
5.61
5.57
49.2
45.9
28.0
38.8
6.27
6.22
67
62
82.7
77.0
58.1
70.2
4.61
4.51
78.2
72.3
54.3
66.7
5.17
5.04
72.8
67.5
49.2
62.9
5.73
5.60
67.0
62.4
45.2
56.2
6.36
6.24
60.8
57.5
41.4
49.7
7.01
6.92
52.8
53.1
34.6
44.4
7.78
7.70
sensible capacity (Btuh)
1.10 x cfm
total capacity (Btuh)
4.5 x cfm
29

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents