Performance data (cont)
48HJ004 (3 TONS)
Temp (F) Air Entering Evaporator — Cfm/BF
Temp (F)
900/0.14
Air Ent
Condenser
Temp (F) Air Entering Evaporator — Ewb
(Edb)
72
67
TC
41.3
37.3
75
SHC
17.5
22.4
kW
2.19
2.14
TC
38.6
34.4
85
SHC
15.2
20.1
kW
2.46
2.40
TC
35.9
31.4
95
SHC
13.0
17.9
kW
2.74
2.68
TC
33.8
29.7
105
SHC
10.9
15.8
kW
3.05
3.00
TC
31.8
28.0
115
SHC
9.0
13.7
kW
3.40
3.36
TC
28.7
26.3
125
SHC
6.9
12.2
kW
3.78
3.73
48HJ005 (4 TONS)
Temp (F)
1200/0.17
Air Ent
Condenser
(Edb)
72
67
TC
52.9
47.5
75
SHC
22.7
28.4
kW
2.87
2.86
TC
49.2
43.8
85
SHC
19.8
25.5
kW
3.26
3.25
TC
45.8
40.1
95
SHC
17.2
22.5
kW
3.71
3.68
TC
41.6
37.0
105
SHC
13.5
19.5
kW
4.20
4.17
TC
37.2
33.2
115
SHC
9.9
16.4
kW
4.73
4.68
TC
32.4
28.1
125
SHC
7.2
12.9
kW
5.29
5.23
LEGEND
BF
— Bypass Factor
Edb — Entering Dry Bulb
Ewb — Entering Wet Bulb
kW
— Compressor Motor Power Input
SHC — Sensible Heat Capacity (1000 Btuh) Gross
TC
— Total Capacity (1000 Btuh) Gross
28
COOLING CAPACITIES, UNITS WITH MOISTUREMISER OPTION
1200/0.17
62
72
67
62
34.3
43.5
39.2
35.9
26.7
19.6
25.5
31.2
2.10
2.21
2.16
2.14
31.6
41.3
37.5
33.3
25.1
17.1
23.2
29.0
2.37
2.47
2.43
2.40
28.8
39.2
35.9
30.6
23.3
14.5
21.1
26.9
2.63
2.76
2.74
2.67
27.4
36.3
32.2
28.7
21.0
12.5
18.9
24.6
2.97
3.09
3.04
2.99
25.5
33.2
28.7
26.5
18.4
10.3
16.8
22.3
3.31
3.45
3.38
3.32
23.4
29.7
25.5
22.9
17.3
7.9
14.5
20.6
3.66
3.84
3.77
3.71
Temp (F) Air Entering Evaporator — Cfm/BF
1450/0.19
Temp (F) Air Entering Evaporator — Ewb
62
72
67
62
41.5
55.7
50.9
47.5
33.4
26.1
34.1
38.9
2.82
2.89
2.87
2.84
37.1
52.1
47.2
43.6
30.4
22.2
29.5
35.8
3.21
3.28
3.26
3.23
32.8
48.2
43.6
39.4
27.3
18.4
24.8
32.6
3.64
3.72
3.69
3.67
29.7
43.2
38.9
35.4
23.9
14.7
21.7
29.2
4.11
4.20
4.17
4.14
27.1
38.4
34.0
30.8
20.7
11.3
18.5
25.6
4.62
4.74
4.71
4.64
24.9
33.8
28.1
27.4
18.3
8.4
14.5
21.9
5.15
5.30
5.25
5.19
1500/0.20
72
67
62
45.5
41.6
38.2
21.5
28.5
35.2
2.24
2.19
2.16
43.5
38.6
35.5
18.9
26.3
32.9
2.51
2.45
2.42
41.3
35.7
32.9
16.1
24.2
30.6
2.80
2.75
2.71
38.1
32.8
30.4
14.0
21.7
28.1
3.12
3.07
3.03
34.9
30.0
27.9
11.9
19.3
25.2
3.48
3.41
3.37
31.3
27.1
25.5
9.2
17.3
22.3
3.87
3.79
3.75
1600/0.21
2000/0.24
72
67
62
72
57.0
51.7
48.1
60.5
25.9
33.7
41.6
29.4
2.89
2.86
2.85
2.90
52.9
47.9
43.7
55.4
22.4
31.1
38.7
24.2
3.28
3.26
3.24
3.28
48.8
44.0
39.3
51.7
19.0
28.1
35.9
20.7
3.72
3.69
3.67
3.74
43.9
39.7
34.7
46.5
15.0
23.7
30.6
16.4
4.20
4.17
4.15
4.22
39.4
35.5
30.0
41.3
11.2
19.7
25.4
12.4
4.73
4.72
4.65
4.74
35.3
30.5
26.6
36.1
16.8
21.1
21.2
9.5
5.29
5.27
5.21
5.30
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
t ldb = t edb –
t lwb = Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h lwb )
h lwb = h ewb –
Where: h ewb = Enthalpy of air entering evaporator coil.
3. The SHC is based on 80 F edb temperature of air entering evapo-
rator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
67
62
55.6
52.1
39.1
47.5
2.88
2.85
51.4
47.0
36.0
44.3
3.26
3.24
47.4
43.0
33.0
41.0
3.70
3.68
41.4
37.5
27.8
35.1
4.19
4.16
35.2
31.9
22.4
28.6
4.72
4.69
32.0
28.7
18.3
24.1
5.29
5.25
sensible capacity (Btuh)
1.10 x cfm
total capacity (Btuh)
4.5 x cfm