Specifications; Pressures; Temperatures; Thermostatic Shut-Down - Mira MYLINE Installation & User Manual

Thermostatic mixer
Table of Contents

Advertisement

SPECIFICATIONS

Pressures

Max Static Pressure: 10 Bar.
Max Maintained Pressure: 5 Bar.
Min Maintained Pressure (Gravity System):
0.1 Bar (0.1 bar = 1 Metre head from cold
tank base to showerhead outlet).
Note! For gravity fed / other low pressure
systems (0.5 bar or below) remove the outlet
flow regulator. Refer to section: 'Installation,
Flow Regulator'.
For optimum performance supplies should be
nominally equal.

Temperatures

Factory Pre-set (Blend) Shower: 43°C.
Optimum Thermostatic Control Range: 35°C
to 43°C (achieved with supplies of 15°C cold,
65°C hot and nominally equal pressures).
Recommended Hot Supply: 60°C to 65°C
Note! The mixing valve can operate at
higher temperatures for short periods without
damage, however this could detrimentally
affect thermostatic performance. For safety
and performance reasons it is recommended
that the maximum hot water temperature is
limited to 65°C.
Cold Water Range: up to 25°C.
Minimum Recommended Differential between
Hot Supply and Outlet Temperature: 12°C.

Thermostatic Shut-down

For safety and comfort the thermostat will
shut off the mixing valve within 2 Seconds if
either supply fails (achieved only if the blend
temperature has a minimum differential of
12°C from either supply temperature).

Connections

The thermostatic mixer can only be installed with
rear supply inlets and the supply pipework must
be connected as follows:
Cold: Top (side nearest temperature control),
15 mm compression.
Hot: Bottom (side nearest flow control), 15
mm compression.
Outlet: 15 mm flat face to hose.
Note! This product does not allow for reversed
inlets and will deliver unstable temperatures if
fitted incorrectly.
Cold

Dimensions

∅42
All dimensions in mm
6
Hot
Outlet
107
59
188
57