Viessmann VITODENS 200-W WB2B Service Instructions For Contractors page 71

80 and 105 kw, wall mounted gas fired condensing boiler, natural gas version
Hide thumbs Also See for VITODENS 200-W WB2B:
Table of Contents

Advertisement

Fault codes
(cont.)
Fault
Const.
Weath.-
code
comp.
on the
display
28
X
30
X
X
38
X
X
40
X
48
X
50
X
X
58
X
X
System char-
Cause
acteristics
Regulates
System flow
without flow
temperature
temperature
sensor lead
sensor (low
broken
loss header)
Burner
Boiler water
blocked
temperature
sensor
shorted out
Burner
Boiler water
blocked
temperature
sensor lead
broken
Mixer closes
Heating cir-
cuit with
mixer M2
flow tem-
perature
sensor
shorted out
Mixer closes
Heating cir-
cuit M2 flow
temperature
sensor lead
broken
No DHW heat-
Cylinder
ing
temperature
sensor
shorted out
No DHW heat-
Cylinder
ing
temperature
sensor lead
broken
Troubleshooting
Measures
Check the low
loss header sen-
sor (see page 82).
Check the boiler
water tempera-
ture sensor (see
page 82).
Check the boiler
water tempera-
ture sensor (see
page 82).
Check the flow
temperature sen-
sor.
Check the flow
temperature sen-
sor.
Check the sensor
(see page 82).
Check the sensor
(see page 82).
71