Viessmann VITODENS 200-W WB2B Service Instructions For Contractors page 54

80 and 105 kw, wall mounted gas fired condensing boiler, natural gas version
Hide thumbs Also See for VITODENS 200-W WB2B:
Table of Contents

Advertisement

Coding
Code 2
(cont.)
Coding in the delivered condition
A9:7
With pump idle time:
Heating circuit pump
"OFF" if the set value
changes through a
change in operating
mode or through a
change in the set room
temperature (only for
weather-compensated
control units)
b0:0
With remote control:
Heating mode/reduced
mode: weather-com-
pensated (only for
weather-compensated
control units; change
the coding only for the
heating circuit with
mixer M2)
b2:8
Heating with room tem-
perature hook-up must
be programmed for re-
mote control and for the
heating circuit: Room
influence factor 8
(only for weather-com-
pensated control units;
change the coding only
for the heating circuit
with mixer M2)
b5:0
With remote control: No
room temperature-com-
pensated heating circuit
pump logic function
(only for weather-com-
pensated control units;
change the coding only
for the heating circuit
with mixer M2)
54
Possible change
A9:0
Without pump idle time
A9:1
With pump idle time; ad-
to
justable from 1 to 15
A9:15
b0:1
Heating mode: weather-
compensated
Reduced mode: with
room temperature hook-
up
b0:2
Heating mode: with room
temperature hook-up
Reduced mode: weather-
compensated
b0:3
Heating mode/reduced
mode: with room tem-
perature hook-up
b2:0
Without room influence
b2:1
Room influence factor
to
adjustable from 1 to 64
b2:64
b5:1
Heating circuit pump
to
logic function; see the fol-
b5:8
lowing table