Check item
When "Connected Device
Are 32 stations or more in total connected?
Information" under "Basic
Settings" of the master station is
Are nine or more authentication class B devices
set to "Mixture of Authentication
connected to P1 or P2 of the master station?
Class B/A or Authentication
Are authentication class A devices in line
Class A Only"
topology?
Other than the master station, are
authentication class B devices in star topology?
In line topology plus star topology, are
authentication class A devices connected with
the master station in line topology?
Is the master station connected with
authentication class B devices via a general-
purpose hub?
Is an authentication class A device connected
between the master station and authentication
class B devices?
Are the master station and authentication class
A devices in line topology?
Are authentication class A devices connected
to each other?
Is a general Ethernet device connected to
places other than the end of the network?
Are an authentication class A device and a
general Ethernet device in line topology?
Do not use general-purpose hubs other than
the NZ2EHG-T8(N) or DT135TX.
Is a general-purpose hub in cascade
connection?
Action
Reduce the total number of station to 31 stations (master station: 1,
slave station: 30) or less.
Reduce the number of authentication class B devices connecting to P1
or P2 of the master station to eight or less for each.
Do not connect authentication class A devices in line topology.
When connecting an authentication class B device and an authentication
class A device, connect them via a general-purpose hub.
Other than the master station, do not connect authentication class B
devices (via general-purpose hub) in star topology.
For line topology with the master station, connect only with
authentication class B devices.
When connecting the master station and an authentication class B
device, connect them in line topology without a general-purpose hub.
Connect the master station and an authentication class B device without
a general-purpose hub.
Connect the master station and an authentication class A device via a
general-purpose hub.
Connect the master station and an authentication class A device via a
general-purpose hub.
Connect authentication class A devices via a general-purpose hub. (Only
one device for each port of a general-purpose hub)
Connect a general Ethernet device at the end of the network.
Do not connect an authentication class A device and a general Ethernet
device. Even if a general Ethernet device is at the end of the network, do
not connect to it.
Use the NZ2EHG-T8(N) or DT135TX.
Do not connect it in cascade connection.
3.4 Troubleshooting by Symptom