Derating Factors As A Function Of Installation Altitude And Ambient Temperature - Siemens SINAMICS S120 Equipment Manual

Chassis liquid cooled power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
2.3 Active Interface Modules
2.3.7

Derating factors as a function of installation altitude and ambient temperature

The cabinet devices and the associated system components are rated for an ambient
temperature of 40 °C and installation altitudes up to 2000 m above sea level.
At ambient temperatures > 40 °C, the output current must be reduced. Ambient
temperatures above 55 °C are not permissible.
At installation altitudes > 2000 m above sea level, it must be taken into account that the air
pressure, and therefore air density, decreases as the height increases. This reduces both
the cooling effect as well as the insulating strength of the air.
As a result of the lower cooling effect, on one hand, the ambient temperature must be
reduced, and on the other hand, the power loss in the chassis unit must also be reduced by
decreasing the output current; whereby ambient temperatures less than 40 °C can be
factored in as countermeasure for compensation.
The following table shows the permissible output currents as a function of installation altitude
and ambient temperature (the permissible correction between installation altitude and
ambient temperatures of < 40 °C – inlet air temperature at the air inlet of the chassis unit – is
taken into account in the specified values).
The values apply under the precondition that a cooling air flow though the units as stated in
the technical specifications is ensured.
As a further measure at installation altitudes of 2000 m and 5000 m, the use of an isolating
transformer is required to reduce transient overvoltages in accordance with EN 60664-1.
Table 2- 14
Current derating for chassis units as a function of ambient temperature (supply air temperature at the air inlet
of the chassis unit) and installation altitude
Installation altitude
above sea level in m
0 ... 2000
... 2500
... 3000
... 3500
... 4000
... 4500
... 5000
56
at an ambient temperature (air intake temperature) of
20 °C
25 °C
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
100 %
97.5 %
98.2 %
Current derating factor (in % of rated current)
30 °C
35 °C
100 %
100 %
100 %
100 %
100 %
98.7 %
100 %
96.3 %
40 °C
45 °C
100 %
93.3 %
96.3 %
Chassis Liquid Cooled Power Units
Manual, (GH7), 01/2011, 6SL3097-4AM00-0BP1
50 °C
55 °C
86.7 %
80.0 %

Advertisement

Table of Contents
loading

Table of Contents