4.4.2.5
Motor connection
Table 4- 11
Motor connection
Note
The total length of the shielded power cables must not exceed 100 m.
4.4.2.6
Protective conductor connections for the equipotential bonding bar
Table 4- 12
Protective conductor connections HF Choke Module
High Frequency Drive
System Manual, (SH2), 04/2015, 6SL3097-4AH10-0BP3
Terminals
U2
V2
W2
PE connection
Terminals
PE connections directly at the
housing to fix the equipotential
bonding bar
Technical data
Threaded bolts: M8
Tightening torque: 13 Nm
For ring cable lugs without insulation (Page 173)
Threaded hole: M8
Tightening torque: 13 Nm
For ring cable lugs without insulation (Page 173)
Connection photograph, see Chapter Electrical connection
(Page 62)
Technical data
Threaded hole: M8
Tightening torque: 13 Nm
For ring cable lugs without insulation
(Page 173)