9.5

Installation

Required tools:
● Slot-head screwdriver (1 x 5.5) for releasing the protective cover
● Torx screwdriver T20 for DC link screws (Torx slot)
Table 9- 2
Installation of the DC link adapter at the HF Damping Module
1. Release and open the protective cover of the DC link.
3. Fix the DC link adapter (1.8 Nm) using the previously
removed DC link screws. Use the right-hand holes
High Frequency Drive
System Manual, (SH2), 04/2015, 6SL3097-4AH10-0BP3
2. Remove the DC link screws.
4. Remove the DC link side cover and close the protective
cover until you hear it engage.
.
DC link adapter
9.5 Installation