Honeywell Accenta Series Engineer's Manual page 26

Table of Contents

Advertisement

Accenta/Optima Engineer's Manual
System Flags
Flag 1 - Options
There are eight options under Flag1 which are described below:
1 = Silent PA
When this flag is set to ON, operating PA will cause a silent PA alarm. Pressing the [1] button toggles the flag
ON or OFF.
2 = RKP PA
When this flag is set to ON, the keypad PA buttons are enabled. Pressing the [2] button toggles the flag ON
or OFF.
3 = Engineer Reset
When this flag is set to ON, an engineer code must be entered to reset the system after Tamper, PA or Fire
alarm. When the flag is set to OFF the system can be reset by the user. Pressing the [3] button toggles the flag
ON or OFF.
4 = PA User Reset
When this flag is set to ON, it permits the user to reset the system after a PA alarm, by pressing the [RESET]
button. The user can reset the system even if the Engineer Reset flag is set to ON. Pressing the [4] button
toggles the flag ON or OFF.
5 = Fire User Reset
When this flag is set to ON, it permits the user to reset the system after a Fire alarm by pressing the [RESET]
button. The user can reset the system even if the Engineer Reset flag is set to ON. Pressing the [5] button
toggles the flag ON or OFF.
6 = Bells in Fire
When this flag is set to ON, the external siren Bell box will sound two seconds On/two second Off during the
fire alarm. Pressing the [6] button toggles the flag ON or OFF.
7 = Zone 7 Fire
When this flag is set to ON it permits zone 7 to be used as a Fire zone. Pressing the [7] button toggles the flag
ON or OFF.
8 = Zone 8 Fire
When this flag is set to ON it permits zone 8 to be used as a Fire zone. Pressing the [8] button toggles the flag
ON or OFF.