F499
Permanent Magnet (PM) Motor Constant 2
Program Motor PM Motor
This parameter is used with synchronous motor applications only.
Contact the TIC Customer Support Center for more information on this
parameter.
Acceleration Time 2
Program Special  ACC/DEC 1 – 4 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency for the 2 Acceleration profile. The
Accel/Decel pattern may be set using F502.
This setting may be adjusted to stabilize unstable Virtual Linear Pump
operation.
This setting is also used to determine the acceleration rate of the UP/DOWN
Frequency Functions.
Note:
An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
acceleration times.
Deceleration Time 2
Program Fundamental ACC/DEC 1 – 4 Settings
This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the 2 Deceleration profile. The
Accel/Decel pattern may be set using F502.
This setting may be adjusted to stabilize unstable Virtual Linear Pump
operation.
This setting is also used to determine the deceleration rate of the UP/DOWN
Frequency Functions.
Note:
A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel, Stall, and Ridethrough settings may lengthen the
deceleration times.
168
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Direct Access Number — F499
Parameter Type — Numerical
Factory Default — 10.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Direct Access Number — F500
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Direct Access Number — F501
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units — Seconds
Q9 Plus ASD Installation and Operation Manual
F501