Mitsubishi 700 Series Instruction Manual page 136

Plug-in option. ethernet multiprotocol communication interface
Hide thumbs Also See for 700 Series:
Table of Contents

Advertisement

Instance
Byte
0
1
70
2
3
0
Reference
71
1
2
3
Mapping Detail
Faulted: Inverter fault signal (0=not faulted, 1=faulted). Maps to inverter register 100 (status word), bit
15 (alarm occurrence).
Warning: This bit is not used (it is always 0).
Running1 (FWD): Running forward status signal (0=not running forward, 1=running forward). Maps to
inverter register 100 (status word), bits 0 and 1. The Running1 bit will be 1 whenever bit 0 (inverter
running) and bit 1 (forward rotation) of the status word are both 1, and will be 0 otherwise. Note that if
Table 33: Input Instances 70 and 71 Detail
Bit 7
Bit 6
Bit 5
Ref
Ctrl
At
From
From
Net
Net
PROTOCOL-SPECIFIC INFORMATION
Bit 4
Bit 3
Speed Actual (Low Byte)
Speed Actual (High Byte)
Running2
Ready
(REV)
Drive State
Speed Actual (Low Byte)
Speed Actual (High Byte)
Bit 2
Bit 1
Running1
Running1
Warning
(FWD)
Bit 0
Faulted
Faulted
9