5.1.9

Modbus command parameters

Addressing the command parameters
You can use MODBUS function code 0x06 on the command parameters.
Table 5-20
Command parameters
Offset
Number
Name
of
registers
60002
1
Reset maximum values
60003
1
Reset minimum values
60004
1
Reset energy counter
60005
1
Synchronization of the
demand period
60006
1
Switching tariff
60007
1
Acknowledge the diagnostics
bit
unsigned long beginning
offset 205)
60008
1
Switching outputs
(if parameterized)
PAC RS485
Manual, 02/2008, A5E02091800B-01
(cf. stored bits in
1)
Unit
Format
-
unsigned short
-
unsigned short
-
unsigned short
Min.
unsigned short
-
unsigned short
-
unsigned short
-
unsigned short
Parameter assignment/Addressing
5.1 MODBUS RTU
Value range from ... to
0
0
0 =
All
1 =
Active Energy
Import Tariff 1
2 =
Active Energy
Import Tariff 2
3 =
Active Energy
Export Tariff 1
4 =
Active Energy
Export Tariff 2
5 =
Reactive Energy
Import Tariff 1
6 =
Reactive Energy
Import Tariff 2
7 =
Reactive Energy
Export Tariff 1
8 =
Reactive Energy
Export Tariff 2
9 =
Apparent
Energy Tariff 1
10 =
Apparent
Energy Tariff 2
1 ... 60
0 =
High tariff
1 =
Low tariff
0 ... ffffh
0 = output 0
OFF
1 = output 0
ON
Access
W
W
W
W
W
W
W
51