Table 5-16 Settings Parameter For Limit Value 2 - Siemens SENTRON PAC RS485 Manual

Expansion module
Hide thumbs Also See for SENTRON PAC RS485:
Table of Contents

Advertisement

Offset
Number of
registers
50087
2
50089
2
Table 5-16
Settings parameter for limit value 2
Offset
Number of
registers
50091
2
50093
2
50095
2
50097
2
PAC RS485
Manual, 02/2008, A5E02091800B-01
Name
Value
Modus ≥ / <
Name
ON/OFF
Hysteresis
Delay
Operation in Limit Logic
Unit
Format
-
float
-
unsigned long
Unit
Format
-
unsigned long
%
float
s
unsigned long
-
unsigned long
Parameter assignment/Addressing
5.1 MODBUS RTU
Value range
13 =
P_L2
14 =
P_L3
15 =
VAR_L1
16 =
VAR_L2
17 =
VAR_L3
18 =
PF_L1
19 =
PF_L2
20 =
PF_L3
21 =
THDV_L1
22 =
THDV_L2
23 =
THDV_L3
24 =
THDI_L1
25 =
THDI_L2
26 =
THDI_L3
27 =
FREQ
28 =
V_LN_AVG
29 =
V_LL_AVG
30 =
I_AVG
31 =
VA_SUM
32 =
P_SUM
33 =
VAR_SUM
34 =
PF_SUM
35 =
V_BAL
36 =
I_BAL
-
0 =
greater than
1 =
less than
Value range
0 =
OFF
1 =
ON
0.0 ... 20.0
0 ... 10
0 =
not used
1 =
AND
2 =
OR
Access
RW
RW
Access
RW
RW
RW
RW
45