Default values and ranges
Default values and ranges for the most commonly used parameters are provided in Appendix A.
2.3
Configure the primary mA output to report mass flow
rate in a user-selected measurement unit
This procedure shows you how to perform these tasks using the display. For all other configuration
tasks, including other options for the mA output, see the configuration sections of this manual.
Note
This procedure assumes that you are starting from the factory-default configuration.
Procedure
1.
Navigate to the configuration menu.
a.
At the transmitter display, activate the Scroll and Select optical switches simultaneously until
SEE ALARM appears on the display.
b.
Activate Scroll repeatedly until OFF-LINE MAINT appears on the display, then activate Select.
c.
Activate Scroll-Select-Scroll.
This operator sequence is a safety precaution, designed to protect the transmitter from
accidental configuration changes caused by unintentional activation of the off-line menu.
Important
If you have enabled a display password, the Scroll-Select-Scroll operator sequence is disabled.
You are required to enter a password before you can continue. The default password is 1234.
d.
Activate Scroll until OFF-LINE CONFG appears on the display, then activate Select.
2.
Set Mass Flow Measurement Unit as desired.
a.
When CONFIG UNITS appears on the display, activate Select.
b.
When UNITS MASS appears on the display, activate Select.
c.
Activate Scroll to view the options for Mass Flow Measurement Unit. When you see the
measurement unit you want to use, activate Select. If STORE/YES? flashes on the display,
activate Select.
d.
Activate Scroll until UNITS EXIT appears on the display, then activate Select.
3.
Set mA Output Process Variable to Mass Flow Rate.
a.
Activate Scroll until CONFIG IO appears on the display, then activate Select.
b.
When AO 1 appears on the display, activate Select.
c.
When AO 1 SRC appears on the display, activate Select.
d.
Activate Scroll to view the options for mA Output Process Variable options. When you see MFLOW,
activate Select. If STORE/YES? flashes on the display, activate Select.
4.
Set Lower Range Value (LRV).
20