Lochinvar EcoShield SHW35-245CE Installation, Commissioning & Maintenance Instructions page 60

Gas fired condensing water heaters
Table of Contents

Advertisement

RELIEF VALVE
At least once a year, the temperature and pressure relief valve and safety valve should be checked to ensure that they operate correctly. To
check the valves, the manual override levers should be operated several times. The valves should seat properly and operate freely.
If water does not flow, drain the heater, remove the inoperative valve and inspect for obstructions or corrosion. Replace with a new valve of the
recommended size as necessary.
FLUE SYSTEM
Examine the exhaust and air intake system every 12 months. Points of inspection are as follows:
1.
Check for obstructions and/or deterioration of flue pipe and terminal. Replace immediately where needed.
2.
Check the terminal for any foreign material and remove as necessary
3.
Check all flue system connections for leakage and reseal as required.
4.
Check that ventilation grilles comply with current regulations.
AIR INTAKE CONNECTION
During the annual maintenance inspection the coupling piece between the fan housing and air inlet tube should be checked to ensure it is
correctly fitted and secure.
CONDENSATE NEUTRALISATION KIT
If fitted, the condensate neutralisation kit will require replacing after 12 months of operation. Please refer to the item specific instructions for
further details.
Check and tighten if required
Fig 15.9 Air intake connection
Coupling Piece
60

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents