10.17 FLUE TERMINAL GUARDING

If a horizontal flue terminal is to be fitted less than 2 metres from ground level or in a location where it can be touched from a window, door or
balcony, a terminal guard must be fitted.
The terminal guard is constructed from plastic-coated mild steel and is suitable for use on condensing appliances only. The guard should be
installed centrally around the terminal ensuring a gap of at least 50mm between the guard and terminal is maintained.