C33 Concentric Vertical Flue Systems; Vertical Flue Terminal Installation - Lochinvar EcoShield SHW35-245CE Installation, Commissioning & Maintenance Instructions

Gas fired condensing water heaters
Table of Contents

Advertisement

10.13 C
CONCENTRIC VERTICAL FLUE SYSTEMS
33
Flue system specifications
MANUFACTURER MUELINK AND GROL (M&G)
TEMPERATURE CLASS T120
FLUE GAS MATERIAL PP
Each concentric Vertical flue kit includes the items shown in the tables below
CONCENTRIC VERTICAL FLUE ASSEMBLY MODELS
SHW35-245,SHW46-325,SHW61-325
COMPONENTS INCLUDED
Item No.
AIR INLET TRANSITION Ø80mm ALU
M75256
M121602
TWIN PIPE TO CONCENTRIC ADAPTOR Ø80/80mm TO Ø80/125mm PP
SAMPLING POINT Ø80/125mm PP
M84471
CONCENTRIC VERTICAL TERMINAL Ø80/125mm PP
M86864
CONCENTRIC HORIZONTAL FLUE ASSEMBLY MODELS
SHW86-410,SHW116-410,SHW146-410
COMPONENTS INCLUDED
Item No.
M75257
AIR INLET TRANSITION Ø100mm ALU
M121605
TWIN PIPE TO CONCENTRIC ADAPTOR Ø100/100mm TO Ø100/150mm PP
M84421
SAMPLING POINT Ø100/150mm PP
LV310754
CONCENTRIC VERTICAL TERMINAL Ø100/150mm PP

10.14 VERTICAL FLUE TERMINAL INSTALLATION

When the water heater is installed as a Type C
1.
Confirm that the roof flashing is correct for the type of roof through which the terminal is to be installed. Section 10.14.1
2.
Determine the desired location for the flue terminal, taking into account minimum distances as detailed in Section 10.3.1 TERMINAL
POSITIONS and the relevant British Standards.
3.
Taking care to protect the appliance from debris and dust, drill a hole in the desired location. The diameter of the hole should be no
more than 10mm greater than the diameter of the air supply pipe of the terminal.
The hole should be drilled from the outside to ensure that no damage is done to the roofing material. Extra care
should be taken to ensure that the hole is drilled vertically.
4.
Install the roof flashing and secure as appropriate.
5.
Carefully insert the roof terminal through the roof flashing and hole in the roof.
Item No SHVF003
Description
Item No SHVF004
Description
appliance, the flue system should be installed as follows:
33
Included
1
1
1
1
Included
1
1
1
1