8.4.3.3
Line/load connection
Table 8- 2
Line/load connection of the Active Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
PE1, PE2
Dimensions for connecting alternative cable lugs, see "Cable lugs" in the Appendix.
1)
Grid infeed
System Manual, 04/2015, A5E03347436A
8.4 Air-cooled Active Line Modules for the grid infeed, chassis format
Technical data
Voltage:
3 AC 320 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 %
•
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
•
Frequency: 47 ... 63 Hz
Connecting thread:
Frame size GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
•
Frame size JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
•
Voltage:
520 ... 750 V DC
•
750 ... 1035 V DC
•
Connections:
Frame size GX: Threaded bolts M6 / 6 Nm for cable lugs in accordance with DIN 46234 /
•
DIN 46235
1)
Frame size JX: d = 13 mm (M12/50 Nm) flat connector for busbar
•
Voltage:
520 ... 750 V DC
•
750 ... 1035 V DC
•
Connections:
Frame size GX: Thread M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
•
DIN 46235
1)
Frame size JX: d = 13 mm (M12/50 Nm) flat connector for busbar
•
Connecting thread:
Frame size GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
•
Frame size JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 / DIN 46235
•
Device overview
1)
1)
1)
1)
151