Table 10-7 Assignment Of Status Bytes - Siemens SIMATIC S7-400H System Manual

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Using I/Os in S7-400H
10.5 Connecting redundant I/Os
Evaluating the passivation status of individual module pairs by means of MODUL_STATUS_WORD
MODUL_STATUS_WORD is located in the instance DB of FB 453 "RED_STATUS". The two
status bytes provide information about the status of individual module pairs.
MODUL_STATUS_WORD is an output parameter of FB 453 and can be interconnected
accordingly.
Table 10-7
Assignment of status bytes
Bit
Meaning
Status byte 1
0
0 = Passivation of module–Low triggered by OB 82
1 = No passivation of module–Low triggered by OB 82
1
0 = passivation of module–Low triggered by OB 82
1 = no passivation of module–Low triggered by OB 82
2
0 = Overflow or underflow (at analog input modules)
1 = No overflow or underflow
3
0 = Channel information is available
1 = Channel information is not available
4
0 = At least one discrepancy time expired (at input modules)
1 = No discrepancy time expired
5
0 = Module pair is discrepant (at input modules)
1 = Module pair is not discrepant
6
0 = Module–Low passivated
1 = Module–Low depassivated
7
0 = Module–High passivated
1 = Module–High depassivated
Status byte 2
0
In the case of module-granular redundancy: Reserve
In the case of channel-granular redundancy:
0 = At least one channel of module-Low is passivated
1 = No channel of module-Low is passivated
1
In the case of module-granular redundancy: Reserve
In the case of channel-granular redundancy:
0 = At least one channel of module-High is passivated
1 = No channel of module-High is passivated
2
0 = No enable for depassivation of module-Low after outgoing event in OB 85
1 = Enable for depassivation of module-Low after outgoing event in OB 85
3
0 = No enable for depassivation of module-High after outgoing event in OB 85
1 = Enable for depassivation of module-High after outgoing event in OB 85
4
0 = No enable for depassivation of module-Low after outgoing event in OB 82
1 = Enable for depassivation of module-Low after outgoing event in OB 82
5
0 = No enable for depassivation of module-High after outgoing event in OB 82
1 = Enable for depassivation of module-High after outgoing event in OB 82
6
0 = Passivation of module–Low triggered by OB 85
1 = No passivation of module–Low triggered by OB 85
7
0 = passivation of module–Low triggered by OB 85
1 = no passivation of module–Low triggered by OB 85
150
System Manual, 09/2007, A5E00267695-03