Table 15-3 Specification Of Fiber-Optic Cables For Outdoor Applications - Siemens SIMATIC S7-400H System Manual

Fault-tolerant systems
Hide thumbs Also See for SIMATIC S7-400H:
Table of Contents

Advertisement

Synchronization modules
15.3 Selecting fiber-optic cables
Table 15-3
Specification of fiber-optic cables for outdoor applications
Cabling
A cable junction is required
between the indoor and
outdoor area
see Figure 15-2
A cable junction is required
between the indoor and
outdoor area
see Figure 15-2
256
Components required
Installation cables for
outdoor applications
including installation cables for
indoor applications as required
Patch cable for indoor
applications
One distribution/junction box
per branch
Installation cables and patch
cables are interconnected by
means of distribution box, using
either ST or SC connectors for
example.
Check the cross-over installation
when you wire the CPUs.
Specification
Installation cables for outdoor applications
1 cable with 4 cores per fault-tolerant system
Both interfaces in one cable
1 or 2 cables with several shared cores
Separate installation of the interfaces in order to
increase availability (reduction of common cause
factor)
Connector type ST or SC, for example, to match
other components; see below
Further specifications you may need to observe for
your plant:
UL certification
Halogen-free materials
Observe further specifications as required for local
conditions:
Protection against increased mechanical stress
Protection against rodents
Water-proofing
Suitable for direct underground installation
Suitable for the given temperature ranges
Avoid spliced cables in the field. Use prefabricated
cables with pulling protection/aids in whiplash design,
including measuring log.
1 cable with 4 cores per fault-tolerant system
Both interfaces in one cable
1 or 2 cables with several shared cores
Separate installation of the interfaces in order to
increase availability (reduction of common cause
factor)
Connector type ST or SC, for example, to match
other components; see below
Further specifications you may need to observe for
your plant:
UL certification
Halogen-free materials
Avoid spliced cables in the field. Use prefabricated
cables with pulling protection/aids in whiplash or
breakout design, including measuring log.
Connector type LC on ST or SC, for example,
to match other components
Connector type ST or SC, for example, to match
other components
System Manual, 09/2007, A5E00267695-03