Alarm   L Atching   ( Prog   >   A Lm.1,   A Lm.2   >   L Tch); Alarm   P Ower-­-On   B Ehavior   ( Prog   >   A Lm.1,   A Lm.2   >   A .P; Alarm   O N   D Elay   ( Prog   >   A Lm.1,   A Lm.2   >   D E - Omega PLATINUM Series User Manual

Temperature, process and strain meters
Hide thumbs Also See for PLATINUM Series:
Table of Contents

Advertisement

PLATINUM   S eries   M eters   U ser's   G uide  
 
 
7.3.7
Alarm   L atching   ( PRoG   >   A LM.1,   A LM.2   >   L tCH)  
Select   t he   A larm   L atching   ( LtCH)   p arameter.  
 
Navigate   t o   t he   d esired   o ption.   O ptions   i nclude   t he   f ollowing:  
 
No   –   Alarm   d oes   n ot   l atch   ( factory   d efault);   t he   A larm   t urns   o ff   w hen   t he   P rocess  
Value   r eturns   t o   a   n on-­‐Alarm   c ondition  
yES   –   Alarm   l atches;   e ven   i f   t he   P rocess   V alue   r eturns   t o   a   n on-­‐Alarm   c ondition,   t he  
Alarm   c ondition   r emains   a ctive   a nd   m ust   b e   u nlatched   u sing  
botH   –   A larm   l atches   a nd   c an   b e   u nlatched   e ither   b y   u sing  
panel   o r   v ia   t he   d igital   i nput    
RMt   –   Alarm   l atches   a nd   c an   b e   u nlatched   o nly   v ia   t he   d igital   i nput  
Select   t he   i ndicated   o ption.  
 
7.3.8
Alarm   N ormally   C losed,   N ormally   O pen   ( PRoG   >   A LM.1,   A LM.2   >  
CtCL)  
Select   t he   A larm   N ormally   O pen   o r   N ormally   C losed   ( CtCL)   p arameter.  
 
Navigate   t o   t he   d esired   o ption.   O ptions   i nclude   t he   f ollowing:  
 
N.o.   –   Normally   o pen:   o utput   i s   a ctivated   w hen   t he   A larm   c ondition   i s   m et   ( factory  
default)  
N.C.   –   Normally   c losed:   o utput   i s   a ctivated   i n   n ormal   c onditions,   b ut   t urned   o ff   i n  
the   A larm   c ondition  
Select   t he   i ndicated   o ption.  
 
 
7.3.9
Alarm   P ower-­‐On   B ehavior   ( PRoG   >   A LM.1,   A LM.2   >   A .P.oN)  
Select   t he   A larm   P ower-­‐On   B ehavior   ( A.P.oN)   p arameter.  
 
Navigate   t o   t he   d esired   o ption.   O ption   i nclude:  
 
yES  –   Alarms   a re   a ctive   a t   p ower-­‐on   a nd   d o   n ot   r equire   c rossing   t he   S etpoint  
(factory   d efault)  
No   –   Alarms   a re   i nactive   a t   p ower-­‐on;   t he   p rocess   r eading   m ust   c ross   t he   A larm  
condition   b efore   b eing   a ctivated  
Select   t he   i ndicated   o ption.  
 
7.3.10
Alarm   O n   D elay   ( PRoG   >   A LM.1,   A LM.2   >   d E.oN)  
Select   t he   A larm   O n   D elay   ( dE.oN)   p arameter.  
 
Set   t he   n umber   o f   s econds   t o   d elay   t riggering   t he   A larm.   ( The   d efault   i s   0 .)   T his   s etting   c an   b e  
 
used   t o   p revent   f alse   A larm   t riggering   w hen   t he   P rocess   V alue   o nly   b riefly   e nters   a n   A larm  
condition.  
Confirm   t he   v alue.  
 
 
 
 
Reference   S ection:   P rogramming   M ode   ( PRoG)  
 
o PER   >   L
.RSt  
o PER   >   L
.RSt   f rom   t he   f ront  
47  
 