SiUS041829E
4.16 Discharge Pipe Temperature Control
F3
Error Code
Method of Error
An error is determined with the temperature detected by the discharge pipe thermistor.
Detection
Error Decision
If the temperature detected by the discharge pipe thermistor rises above A, the compressor
Conditions
The error is cleared when the discharge pipe temperature has dropped below B.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
09/12 class
18 class
If the frequency drops, the temperature is lowered in compensation.
Supposed
Defective discharge pipe thermistor
Causes
Defective electronic expansion valve or coil
Refrigerant shortage
Defective four way valve
Water mixed in refrigerant
Defective stop valve
Defective outdoor unit PCB
Troubleshooting
Reference
Check No.01 Refer to P.112
Reference
Check No.12 Refer to P.114
Reference
Check No.14 Refer to P.115
Note
When replacing the defective thermistor(s), replace the thermistor as ASSY.
Part 6 Service Diagnosis
stops.
A
°C
110
110
(Defective outdoor heat exchanger thermistor or outdoor temperature thermistor)
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Check No. 01
Check the thermistors.
OK
Check No. 12
Check the electronic
expansion valve.
OK
Check No. 14
Check the refrigerant line.
OK
B
°F
°C
°F
230
88
190.4
230
95
203
NG
∗ Discharge pipe thermistor
∗ Outdoor heat exchanger thermistor
∗ Outdoor temperature thermistor
NG
NG
∗ Refrigerant shortage
∗ Four way valve
∗ Water mixed
∗ Stop valve
Troubleshooting
Replace the defective
thermistor(s).
Replace the electronic
expansion valve or the coil.
Refer to the refrigerant line
check procedure.
Replace the outdoor unit
PCB (main PCB).
(R20417)
95