5.10 Discharge Pressure Check
Check No.18
5.11 Outdoor Fan System Check
Check No.19
DC motor
Part 6 Service Diagnosis
Discharge pressure check
High?
YES
Is the stop valve
open?
YES
Is the
connection pipe deformed?
NO
Is the air filter or
indoor/outdoor heat
exchanger dirty?
YES
Check the outdoor fan system.
Is
the outdoor fan
running?
YES
Outdoor fan system is functioning.
NO
NO
YES
NO
NO
Fan motor lead
wire connector
disconnected?
YES
Reconnect the connector.
Replace the compressor.
Open the stop valve.
Replace the pipe installed at
the site.
Replace the compressor.
Clean the dirty air filter or
indoor/outdoor heat exchanger.
(R21121)
NO
Go to Check No. 16.
(R21195)