Facility Setting (cooling at low outdoor temperature)

Outline
This function is limited only for facilities (the target of air conditioning is equipment such as
computers). Never use it in a residence or office (the space where there is a human).
Details
 Cutting jumper J6 on the outdoor unit PCB will extend the operation range to –10°C (14°F).
1. Remove the top plate of the outdoor unit. (09/12 class: 3 screws, 18 class: 6 screws)
2. Remove the front plate. (09/12 class: 4 screws, 18 class: 8 screws)
3. Cut the jumper J6 of the PCB inside.
Reference
For the location of the jumper, refer to pages 20, 21.
Caution
 If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind,
 Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off
 Do not place humidifiers or other items which might raise the humidity in rooms where facility
 Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.
Caution
Replace the remote controller if you cut a jumper unintentionally.
Jumpers are necessary for electronic circuit. Improper operation may occur if you cut any of them.
Part 7 Trial Operation and Field Settings
Installing an air direction adjustment grille (sold separately) will further extend the operation
range to –20°C (–4°F). In these cases, the unit will stop operating if the outdoor temperature
falls below –20°C (–4°F), restarting once the temperature rises above this level.
provide a windbreak wall.
when using facility settings.
settings are being used.
A humidifier might cause dew jumping from the indoor unit outlet vent.