SiUS041829E
1.7

Thermostat Control

Outline
Thermostat control is based on the difference between the room thermistor temperature and the
target temperature.
Details
Thermostat OFF Conditions
 The temperature difference is in the zone A.
Thermostat ON Conditions
 The temperature difference returns to the zone C after being in the zone A.
 The system resumes from defrost control in any zones except A.
 The operation turns on in any zones except A.
 The monitoring time has passed while the temperature difference is in the zone B.
Cooling
Heating
Reference
Refer to Temperature Control on page 23 for details.
Part 4 Functions and Control
(Cooling: 10 minutes, Heating: 10 seconds)
Zone C
Zone C
–1.0°C (–1.8°F)
Zone B
Zone B
–2.0°C (–3.6°F)
Zone A
Zone A
Zone A
Zone A
Zone B
Zone B
1.0°C (1.8°F)
Zone C
Zone C
Room thermistor temperature – target temperature
ON
ON
–0.5°C (–0.9°F)
–1.5°C (–2.7°F)
OFF
OFF
Room thermistor temperature – target temperature
OFF
OFF
1.5°C (2.7°F)
0.5°C (0.9°F)
0°C (0°F)
ON
ON
Main Functions
(R24031)