Em Aq02 And Em Aq04 Analog Output Module Specifications - Siemens Simatic S7 Series System Manual

Hide thumbs Also See for Simatic S7 Series:
Table of Contents

Advertisement

Technical specifications
A.4 Analog inputs and outputs expansion modules (EMs)
Table A- 88
A.4.2

EM AQ02 and EM AQ04 analog output module specifications

Table A- 89
General specifications
Technical data
Article number
Dimensions W x H x D (mm)
Weight
Power dissipation
Current consumption (SM Bus)
Current consumption (24 V DC)
Table A- 90
Analog outputs
Technical data
Number of outputs
Type
Range
Resolution
Full scale range (data word)
Accuracy (25°C / 0 to 55°C)
Settling time (95% of new value)
Load impedance
Output behavior in STOP
616
Connector pin locations for EM AE08 Analog 8 x Inputs (6ES7 288-3AE08-0AA0)
Pin
X10 (gold)
1
L+ / 24 V DC
2
M / 24 V DC
3
Functional Earth
4
AI 0+
5
AI 0-
6
AI 1+
7
AI 1-
EM Analog 2 x outputs (EM AQ02)
6ES7 288-3AQ02-0AA0
45 x 100 x 81
147.1 grams
1.5 W (no load)
60 mA
50 mA (no load)
EM Analog 2 x outputs (EM AQ02)
2
Voltage or current
±10 V or 0 to 20 mA
Voltage mode: 11 bits + sign bit
Current mode: 11 bits
Voltage: -27,648 to 27,648
Current: 0 to 27,648
±0.5% / ±1.0% of full scale
Voltage: 300 μs (R), 750 μ (R), 750 μs (1
μF)
Current: 600 μs (1 mH), 2 ms (10 mH)
Voltage: ≥ 1000 Ω
Current: ≤ 500 Ω
Last value or substitute value (default
value 0)
X11 (gold)
X12 (gold)
No connection
No connection
No connection
No connection
No connection
No connection
AI 2+
AI 4+
AI 2-
AI 4-
AI 3+
AI 5+
AI 3-
AI 5-
EM Analog 4 x outputs (EM AQ04)
6ES7 288-3AQ04-0AA0
45 x 100 x 81
170.5 grams
2.1 W (no load)
60 mA
75 mA (no load
EM Analog 4 x outputs (EM AQ04)
4
Voltage or current
±10 V or 0 to 20 mA
Voltage mode: 11 bits + sign bit
Current mode: 11 bits
Voltage: -27,648 to 27,648
Current: 0 to 27,648
(Refer to the output ranges for voltage and
current (Page 625).)
±0.5% / ±1.0% of full scale
Voltage: 300 μs (R), 750 μ (R), 750 μs (1
μF)
Current: 600 μs (1 mH), 2 ms (10 mH)
Voltage: ≥ 1000 Ω
Current: ≤ 600 Ω
Last value or substitute value (default value
0)
System Manual, 09/2015, A5E03822230-AC
X13 (gold)
No connection
No connection
No connection
AI 6+
AI 6-
AI 7+
AI 7-