Analog Output-Pneumatic (AO-P) Module

The Analog Output-Pneumatic (AO-P) Module is an electric-to-pneumatic interface between
the Fume Hood Controller and the pneumatic actuator. The AO-P Module translates electrical
signals from the Fume Hood Controller into pneumatic signals that command the actuator.
The AO-P Module consists of two industrial grade solenoids that supply or bleed air to the
actuator by using a pulse modulation technique. See Figure 9. Minimum air supply to the AO-
P Module is 18 psi and the maximum is 30 psi. The valves are rated for 24 Vac.
Siemens Building Technologies, Inc.
Figure 8. Pneumatic Actuator.
5.00" (127.0mm)
SUPPLY
EXHAUST
Figure 9. AO-P Module.
Product Overview
3.70"
(94.0mm)
9