Analog Modules
Output ranges
You program the output ranges for voltage and current outputs in STEP 7.
Table 4-83 Output Ranges of the Analog Output Module SM 332; AO 8 x 12 bits
Selected Type of Output
Voltage
Current
Default Settings
The default settings of the module are "Voltage" for the output type and "" 10 V"
for the output range. You can use this combination of output type and output range
without parameterizing the SM 332; AO 8 x 12 bits in STEP 7.
Wire-Break Check
The analog output module SM 332; AO 8 x 12 bits carries out a wire-break check
only for current outputs.
Short-circuit test
The analog output module SM 332; AO 8 x 12 bits carries out a short-circuit test
only for voltage outputs.
4-168
Output Range
1 to 5 V
0 to 10 V
" 10 V
From 0 to 20 mA
From 4 to 20 mA
" 20 mA