Draft Test Procedure - Harman Stove Company Accentra Service Training

Includes all pellet burning units

Advertisement

Remove draft test plug bolt. (9/16 wrench)
Remove hose from draft meter
With meter standing vertical, adjust needle to zero
Hook up the test hose to the "low" port on the meter this is
the port for measuring negative pressure
Attach the other end of the hose to the test port on the stove
using the bolt-tube fitting supplied in the kit
Turn feed adjuster knob to "Test" All motors will run on
high. Record high draft reading (.5" W.C.or more)
After approximately 2 minutes the two blowers will begin
to alternate between high and low. When the combustion
blower is on low, record the low draft reading (.2"W.C.to
.35" W.C.) Remember; This is negative pressure.
Turn unit off of "test"
Remove hose from stove port
Replace draft test plug bolt

Draft Test Procedure

For Units with "test" mode
Harman Pellet Service Training
21