Setting The Position Controller - Siemens SINAMICS G120 Function Manual

Low-voltage inverter; basic positioner (epos) for cu250-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Basic positioner
3.4 Commissioning
3.4.4

Setting the position controller

3.4.4.1
Precontrol and gain
Preconditions and constraints
Before you optimize the position controller, the closed-loop drive speed control must be
optimally set.
Dynamic response and accuracy of the closed-loop position control depend heavily on the
lower-level closed-loop or open-loop control or the motor speed:
● Position control in connection with an optimally set vector control with speed encoder
provides the best results.
● Position control with encoderless vector control (sensorless vector control, SLVC)
provides satisfactory results for most applications. Hoisting/lifting applications require a
speed controller.
● If you operate the position control with the U/f control of drive, then you must take into
account some significant reduction in closed-loop control performance and precision.
Position controllers in hoisting gear
U/f control is not suitable for vertical axes, such as elevating platforms or hoisting gear used
in high-bay racking units, as the axis generally cannot reach the target position as a result of
the limited precision of the U/f control.
Description
Figure 3-5
If the speed control of the converter has an encoder to feedback the actual speed, then
deactivate the integral component T
If you use the position control together with the encoderless vector control (SLVC,
SensorLess Vector Control), the positioning accuracy may be inadequate. With active
integral time, positioning accuracy improves.
42
Position controller with precontrol
of the position controller.
N
Function Manual, 04/2015, FW V4.7 SP3, A5E34257659B AB
Basic positioner

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics series

Table of Contents