5.1.5
Improper laying of shielded cables
Improper laying of shielded cables
Risk of explosion through compensating currents between hazardous area and the
non‑hazardous area.
May cause death or serious injury.
● Shielded cables that cross into hazardous areas should be grounded only at one end.
● If grounding is required at both ends, use an equipotential bonding conductor.
5.1.6
Insufficient isolation of intrinsically safe and non-intrinsically safe circuits
Insufficient isolation of intrinsically safe and non-intrinsically safe circuits
Risk of explosion in hazardous areas.
May cause death or serious injury.
● When connecting intrinsically safe and non‑intrinsically safe circuits ensure that isolation
● Ensure that you observe the device approvals applicable in your country.
5.1.7
Incorrect conduit system
Incorrect conduit system
Risk of explosion in hazardous areas as result of open cable inlet or incorrect conduit system.
May cause death or serious injury.
● In the case of a conduit system, mount a spark barrier at a defined distance from the device
SITRANS FST030 (Modbus)
Operating Instructions, 08/2018, A5E37367739-AD
WARNING
WARNING
is carried out properly in accordance with local regulations for example IEC 60079-14.
WARNING
input. Observe national regulations and the requirements stated in the relevant approvals.
Connecting
5.1 Basic safety notes
31