Dhw; Solar - Viessmann VITODENS 242-F Installation And Service Instructions Manual

3.2 to 26 kw gas condensing/solar storage combi boiler gas council no. 41-819-18; 41-819-19 natural gas and lpg version
Table of Contents

Advertisement

"Boiler"
(cont.)
Coding in the delivered condition
Service status
24:0
"Service" not shown on
display
Filling/Venting
2F:0
Venting program/fill pro-
gram disabled

"DHW"

Select group "DHW" (see page 85).
Coding
Coding in the delivered condition
Set DHW temperature reheating suppression
67:40
For solar DHW heating:
Set DHW temperature
40 °C. DHW reheating is
suppressed above the
selected set temperature.
(DHW heating by the boil-
er only if solar energy is
not sufficient).
Enable DHW circulation pump
73:0
DHW circulation pump:
"ON" according to time
program

"Solar"

Select group "Solar" (see page 85).
Possible change
24:1
"Service" is shown on dis-
play (the address is auto-
matically set and must be
manually reset after the
service)
2F:1
Venting program enabled
2F:2
Fill program enabled
Possible change
67:0
Set DHW temperature ad-
to
justable from 0 to 95 °C
67:95
(limited by boiler-specific
parameters).
Observe the setting of cod-
ing address "56".
73:1
During the time program
to
"ON" from once per hour
73:6
for 5 min to
"ON" 6 times per hour for
5 min
73:7
Constantly "ON"
Code 1
89

Advertisement

Table of Contents
loading

This manual is also suitable for:

B2ua

Table of Contents