Code 2
"Solar"
(cont.)
Coding in the delivered condition
0E:1
Solar yield calculated in
conjunction with
Viessmann heat transfer
medium.
0F:70
The flow rate of the solar
circuit at the maximum
pump speed is set to
7 l/min.
10:0
Target temperature con-
trol switched off (coding
address "11").
11:50
Target temperature con-
trol switched on (code
"10:1"):
Set solar cylinder temper-
ature 50 °C.
Temperature at which the
solar heated water is to
be stratified into the DHW
cylinder.
12:10
Minimum collector tem-
perature (minimum start
temperature for the solar
circuit pump) 10 °C.
"Heating circuit ..."
Select group "Heating circuit ..." (see
page 97).
Coding
Coding in the delivered condition
A0:0
Without remote control
110
Possible change
0E:2
Solar yield calculated in
conjunction with water as
heat transfer medium. Do
not adjust
0E:0
No heat statement
0F:1
Flow rate adjustable from
to
0.1 to 25.5 l/min.
1 step ≙ 0.1 l/min.
0F:255
10:1
Target temperature control
switched on
11:10
Set cylinder temperature
to
adjustable from 10 to
11:90
90 °C.
12:0
Minimum limit disabled
12:1
Minimum collector temper-
to
ature adjustable from 1 to
12:90
90 °C.
Possible change
A0:1
With Vitotrol 200A/200 RF
(automatic recognition)
A0:2
With Vitotrol 300A/300 RF
or Vitocomfort (automatic
recognition)