Further details regarding the individual steps

Cleaning the primary store

Note
According to EN 806, a visual inspection
and (if necessary) cleaning must be car-
ried out no later than two years after
commissioning and thereafter as
required.
1. Drain the primary store.
2. Remove flange cover A.
3. Disconnect the primary store from the
pipework to prevent contamination
from entering the pipe system.
Commissioning, inspection, maintenance
(cont.)
4. Remove loose deposits with a high
pressure cleaner.
!
Please note
When cleaning the inside,
only use plastic cleaning uten-
sils.
2.