Further details regarding the individual steps

Testing the anode earth current with an anode tester

Note
We recommend that the magnesium
anode function is checked annually. This
function test can be carried out without
interrupting operation, by measuring the
earth current with an anode tester.
1. Remove cover A.
2. Remove earth cable B from tab
C.
Commissioning, inspection, maintenance
(cont.)
3. Connect tester (up to 5 mA ) in series
between tab C and earth cable B.
■ If the current measures > 0.3 mA
the anode is OK.
■ If the current measures < 0.3 mA or
if there is no current at all, inspect
the anode visually (see page 68).