Acx: Parameter Back-Up File Missing; Acx: Loading The Parameter Back-Up File Unsuccessful - Siemens SINAMICS S210 Operating Instructions Manual

Servo drive system
Hide thumbs Also See for SINAMICS S210:
Table of Contents

Advertisement

Cause:
When the Control Unit is booted, no complete data set was found from the parameter back-up files. The last time that the
parameterization was saved, it was not completely carried out.
It is possible that the backup was interrupted by switching off or withdrawing the memory card.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = 01 hex:
Power up was realized without data backup. The drive is in the factory setting.
aa = 02 hex:
The last available backup data record was loaded. The parameterization must be checked. It is recommended that the
parameterization is downloaded again.
dd, cc, bb:
Only for internal Siemens troubleshooting.
See also: p0977
Remedy:
- download the project again using the commissioning tool.
- save all parameters (p0977 = 1 or "copy RAM to ROM").
See also: p0977 (Save all parameters)
Reaction upon F:
Servo: NONE (OFF1, OFF2, OFF3)
Acknowl. upon F: IMMEDIATELY
F01036 (A)

ACX: Parameter back-up file missing

Message value:
%1
Drive object:
All objects
Reaction:
Servo: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
Cause:
When downloading the device parameterization, a parameter back-up file PSxxxyyy.ACX associated with a drive object
cannot be found.
Fault value (r0949, interpret hexadecimal):
Byte 1: yyy in the file name PSxxxyyy.ACX
yyy = 000 --> consistency back-up file
yyy = 001 ... 062 --> drive object number
yyy = 099 --> PROFIBUS parameter back-up file
Byte 2, 3, 4:
Only for internal Siemens troubleshooting.
Remedy:
If you have saved your project data using the commissioning tool, carry-out a new download for your project.
Save using the function "Copy RAM to ROM" or with p0977 = 1.
This means that the parameter files are again completely written into the non-volatile memory.
Note:
If the project data have not been backed up, then a new first commissioning is required.
Reaction upon A: NONE
Acknowl. upon A: NONE
F01038 (A)

ACX: Loading the parameter back-up file unsuccessful

Message value:
%1
Drive object:
All objects
Reaction:
Servo: NONE (OFF1, OFF2, OFF3)
Acknowledge:
IMMEDIATELY
SINAMICS S210 servo drive system
Operating Instructions, 12/2017, A5E41702836B AA
Faults and alarms
13.2 List of faults and alarms
301