Blizzard Turbo Split System Manual
To adjust low fan speed:
While in OFF mode, enter programming mode by pressing the MODE and minus (-) keys for three seconds. The display will
flash "PO" during the three seconds. After the three-second flash, a flashing 1 will appear on the display, which is function #1.
While in program mode, the OFF LED will flash, which indicates program mode. Scroll through the function numbers by
pressing the plus (+) or minus (-) key until #5 is displayed. Press the MODE key and the current value is displayed. The low fan
LED will flash. Factory default is 38. Range is 2 to 57. Use the plus (+) or minus (-) key to change value and then, press the fan
key once to save information and continue programming or press the fan key twice to save and exit program mode.
NOTE: For most efficient operation of your system, you should normally keep the low fan speed at the highest
possible setting consistent with a comfortable noise level. Running the fan speed too slow can damage the
compressor.
Table 2: PROGRAMMABLE FUNCTION CHART
Programmable Function
Fahrenheit/Celsius
Low Fan Speed
High Fan Speed
Fan Mode
AC Line Voltage Calibration
Temperature Calibration
Software Version
Software Revision
High Pressure Switch Test
LED Test
LED Sleep Mode
Power Saver Mode
L-3448 ENGLISH
Qt Display Indicators
Displays F
OFF mode flashes
Displays 38
OFF mode flashes
Low fan speed LED
Displays 60
OFF mode flashes
All fan speed LED
Displays C
OFF mode flashes
Displays last two digits of line voltage
OFF mode flashes
Displays inside temperature
OFF mode flashes
Displays version #
OFF mode flashes
Displays revision #
OFF mode flashes
Displays OA or FA
OFF mode flashes and COOL LED flashes
(dot in upper-left corner of display is lit if
compressor is on)
Displays all LEDs
OFF mode flashes
Displays ON=LEDs
or SL=LEDs
Dims settings 10 seconds from last key
touched
Displays "—"
OFF mode flashes
OPERATING THE SYSTEM WITH QT CONTROLS
Function #
Factory
Setting
2
F
5
38
6
85
7
C
8
9
10
n/a
11
n/a
12
OA=Okay
FA=Fault
13
Lights all
LEDs
14
ON
15
"---" =
Normal mode
Range
°F or °C
2 to 57
41 to 99
C or I
±1%
±1%
n/a
n/a
n/a
n/a
ON=Continuous
SL=Sleep mode
"---" =
Normal mode
P1=Power
saver mode
19