Table 6-1. Rosemount 644 Troubleshooting Table for 4-20 mA Output
Symptom or
Potential
issue
source
Sensor
Element
Low or No
Loop
Output
Wiring
Electronics
Troubleshooting
Corrective action
Connect a Field Communicator and enter the transmitter test mode to isolate
a sensor failure.
Check the process variable to see if it is out of range.
Check for adequate voltage to the transmitter. It should be 12.0 to 42.4 Vdc
(over entire 3.75 to 23 mA operating range).
Check for shorts and multiple grounds.
Check for proper polarity at the signal terminal.
Check the loop impedance.
Connect a Field Communicator and enter the Loop test mode.
Check wire insulation to detect possible shorts to ground.
Connect a Field Communicator and check the sensor limits to ensure
calibration adjustments are within the sensor range.
Section 6: Troubleshooting