A built-in high cutout stop is an integral part of these
controls and may be adjusted quickly and easily in the
field. Product Number A19BAG-1 is especially
designed for portable heaters. It is supplied with a
6 ft cord, 120 V.A.C. polarized plug, and a chain hanger
kit.

Optional Constructions

Note: For most prompt service, select controls listed
under "Specifications," below. If these are not entirely
suitable for your application, then the following
variations are available.
Adjustable Differential: Available at extra cost.
Armored Capillary: Single braided copper armor may
be supplied at extra cost.
Capillary Tube: Additional length of capillary over
6 ft available at extra cost. Extra length in 2 ft
increments from 6 ft to 10 ft; over 10 ft in 5 ft
increments.
Contact Unit: Close differential or special close
differential may be supplied.
Mounting Bracket: Optional at extra cost.

Specifications

Product
Number
Appl.
Action
A19AAB-4
Fluid
Opens
Cutout
on rise
A19AAB-7
Industrial
Opens
Oven
on rise
A19AAB-
Industrial
Opens
10
Oven
on rise
A19AAC-1
Dual Fuel
SPDT
Change-
over
A19AAC-9
Fluid
SPDT
Cutout
A19AAE-3
Crop
Opens
Drying
on rise
A19ADB-2
Hot
Opens
Water
on rise
Cutout;
Manual
Reset
A19ADN-1
Warm
Opens
Air;
on rise
Manual
Reset
A19ADP-1
Warm
SPDT
Air;
Manual
Reset
A19BAB-3
Heating
Opens
on rise
A19BAC-1
Farm
SPDT
Thermost
at Heat or
Ventilate
A19BAG-1
Portable
Opens
Heater
on rise
* Maximum bulb temperature which the element can withstand at infrequent intervals during life of control, such as shipping conditions. This is not the
temperature at which the control can withstand on repeat cycles.
2 A19 Product Bulletin
Range
Diff.
*Max. Bulb
°F (°C)
°F (°C)
Temp. °F
(°C)
30 to 110
3 (1.7)
140 (60)
(-1 to 43)
100 to 300
7 (3.9)
350 (177)
(38 to 149)
200 to 550
10 (5.6)
620 (327)
(93 to 288)
-30 to 50
5 (2.8)
140 (60)
(-34 to 10)
100 to 240
6 (3.3)
290 (143)
(38 to 121)
80 to 180
2 (1.1)
200 (93)
(27 to 82)
100 to 240
Lockout
290 (143)
(38 to 121)
100 to 240
Lockout
290 (143)
(38 to 121)
100 to 240
Lockout
290 (143)
(38 to 121)
30 to 95
3 (1.7)
140 (60)
(0 to 35)
30 to 110
3 (1.7)
140 (60)
(0 to 43)
35 to 95
3 (1.7)
140 (60)
(0 to 35)
Types A19AAB, A19AAC, A19BAB, A19BAC
Volts AC
Full Load Amps.
Locked Rotor Amps.
Non-inductive or
Resistance Load Amps.
(Not Lamp Load)
Pilot Duty - 125 VA @ 24 to 600 VAC
* SPST Rating
Types A19AAE
Volts AC
Full Load Amps.
Locked Rotor Amps.
Non-inductive or
Resistance Load Amps.
(Not Lamp Load)
Pilot Duty - 125 VA @ 24 to 277 VAC
Types A19AAB, A19AAC, A19ADB (Hot Water Models)
Volts AC
Full Load Amps.
Locked Rotor Amps.
Non-inductive or
Resistance Load Amps.
Pilot Duty - 125 VA @ 24 to 600 VAC
Bulb
Bulb
Bulb
Style
Size
Well
Length
(in.)
1
3/8 x
WEL14A-
4-15/16
602R
1
3/16 x
10-1/8
1
3/16 x
5-5/8
1
3/8 x
Outdoor
4-1/16
Shield
Supplied
1
3/8 x
WEL14A-
3-9/16
602R
7
1-1/8 x
1-1/4
Copper
Coil
2
0.290 x
Direct
2-11/16
Immersion
1/2 in. NPT
Conn.
1
3/8 x 3
WEL14A-
602R
1
3/8 x 3
WEL14A-
602R
3
Coil
3
Coil
3
Coil
120
208
16.0
9.2
96.0
55.2
* 22 Amps. 120 to 277 VAC
120
208
6.0
3.4
36.0
20.4
10 Amps. 120 to 277 VAC
120
10.0
60.0
10.0
Cap.
Bulb
Cover
Suppor
Plain
Scale
(ft.)
t (in.)
6
3
X
6
X
6
X
6
3
X
6
3
X
10
X
None
X
6
3
X
6
3
X
None
X
None
X
None
X
240
8.0
48.0
240
3.0
18.0
240
6.0
36.0
6.0
Range Adjuster
Screw-
Knob
driver
X
X
X
X
X
X
X
X
X
X
X
X