Linear Application
Linear Applications, see Initialization Procedure (Page 50)
3.19

Parameter 6.SCUR

Default setting is: "4 mA".
● From AUT or MAN mode, press
Now observe the parameter name in the lower right corner.
● Continue to press the
● If it says "0 mA", press the
● To return to Automatic mode, press and hold the
● The unit will now be in Manual mode.
● Press the
3.20

Re-Initialization Positioner

See Initialization Procedure (Page 50)
PS2 Troubleshooting Guide
Service Manual, 03/2017, A5E36661550-AA
button for 5 seconds.
button until "SCUR" parameter is reached.
button to change this to "4 mA".
button one time to return to Automatic mode.
Troubleshooting Procedures
3.19 Parameter 6.SCUR
button for 5 seconds.