ULPG: Can be connected to the inlet fitting directly. The
pressure must be checked to ensure it is operating at
2.75kPa. A separate test point fitting must be installed
between the piping & the appliance for the pressure to
be checked to ensure it is operating at 2.75kPa.
2.3
Caution – This cooker may only be installed and operated in rooms
permanently ventilated in accordance with current regulations. For
proper operation of a gas appliance it is essential for the air necessary
for combustion of the gas to be able to flow naturally into the room. Air
must flow directly into the room through openings in its outside walls.
This (these) opening (s) must have a free passage cross-section of at
least 100 cm
device. These openings must be constructed so that they cannot be
obstructed indoors or outdoors, and should preferably be close to the
floor on the side opposite to the combustion gas discharge point. If it is
not possible to make the openings in the room where the cooker is
installed, the necessary air may be taken from an adjoining room,
proveded it is not a bedroom or a room with fire risk.
2.4
Extract from AS5601
8
Instructions for the installer

Room ventilation

2
, or 200 cm
Clearance above and around domestic cookers
2
for appliances not equipped with gas safety