Electric Characteristics - Daikin 2MXS-N Series Engineering Data

Multi-split type air conditioners, r410a, inverter
Hide thumbs Also See for 2MXS-N Series:
Table of Contents

Advertisement

EDUS121503A

11. Electric Characteristics

Outdoor Unit
2MXS18NMVJU
3MXS24NMVJU
4MXS36NMVJU
Symbols:
MCA
: Min. circuit amps (A)
MFA
: Max. fuse amps (A)
MSC
: Max. current during starting compressor (A)
RLA
: Rated load amps (A)
OFM
: Outdoor fan motor
W
: Fan motor rated output (W)
FLA
: Full load amps (A)
Multi-Split Type Air Conditioners 2/3/4MXS-N Series
Power Supply
Hz - Volts
Voltage Range
60 - 208
Max. 60 Hz 253 V
Min. 60 Hz 187 V
60 - 230
60 - 208
Max. 60 Hz 253 V
Min. 60 Hz 187 V
60 - 230
60 - 208
Max. 60 Hz 253 V
Min. 60 Hz 187 V
60 - 230
Compressor
MCA
MFA
MSC
15.8
20
14.0
18.7
20
15.5
19.75
20
17.5
Notes:
1. RLA is based on the following conditions.
Cooling
Indoor temp.: 80°FDB (27°CDB) / 67°FWB (19°CWB)
Outdoor temp.: 95°FDB (35°CDB)
2. Voltage range
Units are suitable for use on electrical systems where voltage
supplied to unit terminal is not below or above listed range limits.
3. Maximum allowable voltage variation between phases is 2%.
4. MCA represents maximum input current.
MFA represents capacity which may accept MCA.
5. Select wire size based on the value of MCA.
6. MFA is used to select the circuit breaker and the ground fault
circuit interrupter (earth leakage circuit breaker).
7. Be sure to install an earth leak detector.
(This unit uses an inverter, which means that an earth leak
detector capable of handling high harmonics must be used in
order to prevent malfunctioning of the earth leak detector.)
Electric Characteristics
OFM
RLA
W
FLA
14.0
56
0.37
15.5
51
0.33
17.5
75
0.50
3D093255
299
1