Multi-pump control
Hide thumbs Also See for SINAMICS V20:

Advertisement

Setting parameters
Parameter
Function
P1080[0...2] Minimum frequency [Hz]
P1082[0...2] Maximum frequency [Hz]
P1200
Flying start
P2373[0...2] Motor staging hysteresis [%]
P2374[0...2] Motor staging delay [s]
P2375[0...2] Motor destaging delay [s]
P2376[0...2] Motor staging delay override
[%]
P2377[0...2] Motor staging lockout timer [s]
SINAMICS V20 multi-pump control
Operating Manual, 05/2018, A5E43416874-002
Setting
This parameter sets minimum motor frequency at which motor will run
irrespective of frequency setpoint. The value set here is valid both for
clockwise and for counterclockwise rotation.
Range: 0.00 to 550.00 (default setting: 0.00)
This parameter sets maximum motor frequency at which motor will run
irrespective of the frequency setpoint. The value set here is valid for both
clockwise and counterclockwise rotation.
Range: 0.00 to 550.00 (default setting: 50.00)
Starts inverter onto a spinning motor by rapidly changing the output fre-
quency of the inverter until the actual motor speed has been found. Then,
the motor runs up to setpoint using the normal ramp time.
Settings 1 to 3 search in both directions:
= 0: Flying start disabled
= 1: Flying start always active
= 2: Flying start active after power on, fault, OFF2
= 3: Flying start active after fault, OFF2
Settings 4 to 6 search only in the direction of the setpoint:
= 4: Flying start always active
= 5: Flying start active after power on, fault, OFF2
= 6: Flying start active after fault, OFF2
Range: 0 to 6 (default setting: 1)
P2373 is a percentage of PID setpoint that PID error r2273 must be ex-
ceeded before staging delay starts.
Range: 0.0 to 200.0 (default setting: 20.0)
This parameter defines the time that PID error r2273 must exceed motor
staging hysteresis P2373 before staging occurs.
Range: 0 to 650 (default setting: 30)
This parameter defines the time that PID error r2273 must exceed motor
staging hysteresis P2373 before destaging occurs.
Range: 0 to 650 (default setting: 30)
P2376 as a percentage of PID setpoint. When the PID error r2273 ex-
ceeds this value, a motor is staged / destaged irrespective of the delay
timers.
Range: 0.0 to 200.0 (default setting: 25.0)
Note: The value of this parameter must always be larger than staging
hysteresis P2373.
This parameter defines the time for which delay override is prevented after
a motor has been staged or destaged.
Range: 0 to 650 (default setting: 30)
Pump switch-in/switch-out
15