Removal Of Thermistors - Daikin RMKS112EV1A Service Manual

Removal procedure
Hide thumbs Also See for RMKS112EV1A:
Table of Contents

Advertisement

Outdoor Unit
1.4

Removal of Thermistors

Procedure
Step
1
For the details of the
removal of the outdoor
temperature thermistor
(R1T), see the points
on the right column.
2
Pull out the discharge
pipe thermistor (R2T).
Suction pipe thermistor 2 (R5T)
Discharge pipe thermistor (R2T)
3
Pull out the suction pipe
thermistors (R3T)
(R5T).
4
Pull out the subcooling
thermistor (R6T) and
the liquid pipe
thermistor (R7T).
5
Pull out the outdoor
heat exchanger
thermistor (R4T).
14
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Liquid pipe thermistor
(R7T)
Subcooling
thermistor (R6T)
Suction pipe
thermistor 1 (R3T)
Outdoor heat exchanger
thermistor (R4T)
(R12975)
Si181180
Points
Preparation
Remove the front panel (2)
and the right side panel
according to the "Removal of
Outer Panels".
Removal of the outdoor
temperature thermistor
(R1T)
Hooks (2 places)
Right side panel
Notch
Fixing plate for thermistor (R1T)
Stopper
Removal
direction
Outdoor temperature thermistor
Marking (yellow)
(R13061)
When reassembling, pass
the outdoor temperature
thermistor through the hole
of the tube plate so as the
yellow marking comes to the
inside edge of the tube plate.