Outdoor Unit
1.3

Removal of Outdoor Fans / Fan Motors

Procedure
Step
1
Remove the nuts which
fixing the outdoor fan.
12
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Front panel (1)
Discharge
grille
Outdoor fan
Nut with a washer
Points
Preparation
Remove the discharge grille,
front panels (1) and (2), and
piping cover (front),
according to the "Removal of
Outer Panels".
(R9241)
Nut size : M8
When reassembling, align
the
mark of the outdoor
fan with the D-cut section of
the motor shaft.
(R12974)
Removal Procedure
Si181180
13 mm
(R12301)