Removal Of Outdoor Fan / Fan Motor - Daikin RN50HV1A Service Manual Removal Procedure

5.0 kw class outdoor unit

Advertisement

Si011084

2. Removal of Outdoor Fan / Fan Motor

Procedure
Step
1
Disconnect the relay
connector for the fan
motor.
2
Remove the 2 screws
of the fan motor fixing
plate.
3
Lift up and remove the
fan motor fixing plate.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure
Removal of Outdoor Fan / Fan Motor
Points
(R5401)
(R5402)
Be careful so as not to
damage the top part of the
outdoor heat exchanger fins.
(R5403)