Technical Specifications; Vg1000 Series Forged Brass Ball Valves (Part 1 Of 2 ) - Johnson Controls VG1000 Series Installation Instructions Manual

Forged brass ball valves
Table of Contents

Advertisement

Technical Specifications

VG1000 Series Forged Brass Ball Valves (Part 1 of 2 )

1
Service
Fluid Temperature Limits
Maximum Fluid Temperature
Limits
Valve Body Pressure/
Temperature Rating
Maximum Closeoff Pressure
Maximum Recommended Operating Pressure
Drop
Flow Characteristics
2
Rangeability
Minimum Ambient Operating
Temperature
Maximum Ambient
3
Operating Temperature
Leakage
End Connections
Water
Steam
212°F (100°C)
284°F (140°C)
Water
Steam
Two-Way
Three-Way
-4°F (-20°C)
-22°F (-30°C)
-40°F (-40°C)
140°F (60°C)
VG1000 Series Forged Brass Ball Valves Installation Instructions
Hot Water, Chilled Water, 50/50 Glycol Solutions, and
15 psig (103 kPa) Saturated Steam for HVAC Systems
VG12x1 and VG18x1 Series: 23 to 203F (-5 to 95C)
VG12x5 and VG18x5 Series: -22 to 284F (-30 to 140C)
VG12x1 Series: Not Rated for Steam Service
VG12x5 Series: 15 psig (103 kPa) at 250°F (121°C)
VA9104
VA9300
VA9203
VA9208
VA9104 with M9000-561 Thermal Barrier
VA9300 with M9000-561 Thermal Barrier
VA9203 with M9000-561 Thermal Barrier
VA9208 with M9000-561 Thermal Barrier
VG1241, VG1245, VG1841, and VG1845 Series:
580 psig (4,000 kPa) at 203°F (95°C) (PN40)
464 psig (3,196 kPa) at 284°F (140°C) (PN40)
VG1275 and VG1875 Series:
300 psig (2,067 kPa)
VG1295 and VG1895 Series:
300 psig (2,067 kPa)
15 psig (103 kPa) Saturated Steam
200 psig (1,378 kPa)
50 psig (340 kPa)
Equal Percentage
Equal Percentage Flow Characteristics of In-line Port A (Coil) and
Linear Flow Characteristics of Angle Port B (Bypass)
Greater than 500:1
VA9104 and M9104 Series Non-Spring Return Actuators
VA9203 Series Spring Return Actuators
VA9300 Series Non-Spring Return Actuators
VA9208 Series Spring Return Actuators
VA9104 and VA9300 Series Non-Spring Return Actuators
VA9203 and VA9208 Series Spring Return Actuators
0.01% of Maximum Flow per ANSI/FCI 70-2, Class 4
(Two- and Three-Way Control Port)
1% of Maximum Flow for Three-Way Bypass Port
National Pipe Thread (NPT): 1/2 to 2 in. (DN15 to DN50)
Sweat: 1/2 to 1 in. (DN15 to DN25)
Use a low melting point solder.
Press (ProPress compatible): 1/2 to 1 in. (DN15 to DN25)
Press end connections are designed to work with RIDGID pressing
tools.
12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents