Technical Specifications - Johnson Controls IOM3731 Installation Manual

Input/output module
Table of Contents

Advertisement

Accessories
Table 8: Accessories ordering information
Product code number
MS-DIS1710-0
TP-2420
Y65T31-0
AS-XFR050-0
AP-TBK4SA-0
AP-TBK4FC-0
AP-TBK3PW-0
WNC1800/ZFR182x Pro
Wireless field Bus System
ZFR1800 Series Wireless
Field Bus System
NS Series Network
Sensors
WRZ Series Wireless
Room Sensors
Mobile Access Portal
(MAP)Gateway

Technical specifications

Table 9: IOM3731 technical specifications
Product Code Number
Supply Voltage
Power Consumption
Ambient Conditions
Addressing
Communications Bus
Processor
Memory
Input and Output Capabilities
Terminations
Mounting
Housing
Description
Local Controller Display
Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in. Primary Leads and
Secondary Screw Terminals, Class 2
Note: Additional Y6x-x Series transformers are also available. Refer to the Series Y63, Y64, Y65, Y66,
and Y69 Transformers Product Bulletin (LIT-125755) for more information.
Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure
Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack of 10
Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack of 10
Replacement Power Terminal Blocks, 3-Position, Gray, Bulk Pack of 10
This system is used for installations that support BACnet/IP but can also coexist with the ZFR1800 Series
when installed under the same supervisor (i.e., network engine). Refer to the WNC1800/ZFR182x Pro Series
Wireless Field Bus System Product Bulletin (LIT-12012320) for a list of available products.
This system is used for installations that only support BACnet MS/TP. Refer to the ZFR1800 Series Wireless
Field Bus System Product Bulletin (LIT-12011336) for a list of available products.
Refer to the NS Series Network Sensors Product Bulletin (LIT-12011574) for specific sensor model descriptions.
Refer to the WRZ Series Wireless Room Sensors Product Bulletin (LIT-12000653) for specific sensor model
descriptions.
Refer to the Mobile Access Portal Gateway Catalog Page (LIT-1900869) to identify the appropriate product for
your region.
MS-IOM3731-x Input/Output Module
24 VAC (nominal, 20 VAC minimum/30 VAC maximum), 50/60 Hz, power supply Class 2
(North America), Safety Extra-Low Voltage (SELV) (Europe)
14 VA maximum for IOM3731-0A only
Operating: 0°C to 50°C (32°F to 122°F); 10% to 90% RH noncondensing
Storage: -40°C to 80°C (-40°F to 176°F); 5% to 95% RH noncondensing
DIP switch set; valid controller device addresses 4–127 (Device addresses 0–3 and 128–255
are reserved and not valid addresses.)
BACnet MS/TP, RS-485:
3-wire FC bus between the supervisory controller and other controllers
4-wire SA bus between controller, network sensors and other sensor/actuator devices,
includes a lead to source 15 VDC supply power (from controller) to bus devices.
H8SX/166xR Renesas
640 KB Flash Memory and 128 KB Random Access Memory (RAM)
8 - Binary Inputs: Defined as Dry Contact Maintained or Pulse Counter/Accumulator
Mode
8 - Binary Outputs: Defined as 24 VAC Triac (external source power only)
Input/Output: Fixed Screw Terminal Blocks
SA/FC Bus and Supply Power: 4-Wire and 3-Wire Pluggable Screw Terminal Blocks
SA/FC Bus Port: RJ-12 6-Pin Modular Jacks
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface
with three integral mounting clips on controller
Enclosure material: ABS and polycarbonate UL94 5VB; Self-extinguishing, Plenum Rated
Protection Class: IP20 (IEC529)
32-bit microcontroller
®
IOM3731 Input/Output Module Installation Guide
13