Installing
3.2 Connecting
3.2
Connecting
3.2.1
Connecting the inverter and inverter components to the line supply
Danger to life caused by high leakage currents for an interrupted protective conductor
The drive components conduct a high leakage current via the protective conductor.
Touching conductive parts when the protective conductor is interrupted can result in death
or serious injury.
• Dimension the protective conductor as stipulated in the appropriate regulations.
Dimensioning the protective conductor
Observe the local regulations for protective conductors subject to an increased leakage
current at the site of operation.
①
②
③
④
16
WARNING
Protective conductor for line feeder cables
Protective conductor for inverter line feeder cables
Protective conductor between PE and the electrical cabinet
Protective conductor for motor feeder cables
Compact Operating Instructions, 11/2016, FW V4.7 SP6, A5E39339884B AA
SINAMICS G120C, FSD ... FSF inverters